Inexplicable electrical faults may be caused by short circuiting due to incorrectly installed WAGO junction blocks.
The photos below show correct and incorrect orientation for WAGO junction blocks.
Correct Release Tabs on same side (View from above) |
Correct -Blocks facing same way |
Incorrect Release Tabs on opposite sides (View from above) |
Incorrect - Blocks facing opposite ways. |
Incorrect orientation of WAGO junction blocks results in circuits shorting intermittently, which in turn causes electrical faults. The faults caused depend on which blocks are shorting.
Faults caused by incorrectly orientated blocks are more likely to occur when there is high moisture, as moisture provides a path between the blocks causing them to short. Therefore, as an example, a fault may occur early on a winter morning, but not in the middle of the day.
The easiest way to identify an incorrectly orientated block is to look at the positions of the release tabs (See photos above).
If the tabs are not all on the same side of the DIN rail, then a block (or blocks) are orientated incorrectly.
To correct this;